Introducing AR Power's latest innovation, the AR PowerMAX. This cutting-edge double-conversion online UPS boasts an impressive output power factor of 0.9, delivering unparalleled power density and a remarkable 12.5% increase in power compared to conventional UPS units with similar specifications.
Equipped with advanced DSP (Digital Signal Processing) technology and active input power factor correction, the AR PowerMAX ensures superior output voltage stability, power quality, and performance under all circumstances. With its dual mains inputs, this UPS guarantees unmatched power reliability, even in regions plagued by poor power conditions. Experience the next level of power protection and performance with AR PowerMAX.
THREE PHASE/ SINGLE PHASE MODELS | Harga Satuan (Rp.), Eskalasi (Varian 15%) | |||
---|---|---|---|---|
08 (3/1) | 10 (3/1) | 15 (3/1) | 20 (3/1) | |
INPUT | ||||
Rated power (kVA) | 8 | 10 | 15 | 20 |
Rated voltage (V) | 400 Vac three-phase | |||
Voltage range | ±20% | |||
Frequency range | 45/65 Hz | |||
Power factor | 0.8 (0.9 in CLEAN version) | |||
BYPASS | ||||
Rated current (A) | 35 | 43 | 65 | 87 |
Rated voltage (V) | 230 Vac single-phase | |||
Permitted voltage range | ±15% (selectable from ±10% to ±25% from front panel) | |||
Rated frequency | 50/60 Hz (autorange) | |||
Permitted frequency range | ±2% (selectable from ±1% to ±5% from front panel) | |||
Standard features | BackFeed protection; separate bypass line | |||
BATTERIES | ||||
Type | Maintenance-free sealed lead-acid | |||
Maximum recharge current (A) | 0.2xC10 | |||
RECTIFIER OUTPUT | ||||
Maintenance Voltage | Variable acc. to temperature (-0.5 Vx°C) | |||
Ripple | <1% | |||
INVERTER OUTPUT | ||||
Rated power (kVA) | 8 | 10 | 15 | 20 |
Rated voltage (V) | 6.4 | 8 | 12 | 16 |
Number of phases | single-phase | |||
Rated voltage (V) | 220/230/240 | |||
Rated current (A) | 35 | 43 | 65 | 87 |
Regulation of output voltage | 200-244 V phase/neutral (from control panel) ±5% | |||
Crest factor (Ipeak/Irms) | 3:1 | |||
Waveform | Sinewave | |||
Static stability | ±1% | |||
Dynamic stability | ±5% in 5ms | |||
Frequency | same as the input (autorange) | |||
Overload | 125% 150% 200% of the rated current for 10'/1'/7" | |||
Frequency stability | ±0.05% on mains failure | |||
±2% (selectable from ±1% to ±5% from front control panel) with mains supply present | ||||
ENVIROMENTAL Remote Signalling | volt free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm, output 0.5A/42V) | |||
Remote Controls | EPO and bypass | |||
Operating temperature | 0-40°C | |||
Relative humidity | 95% (non condensing) | |||
Color | Light grey RAL 7035 | |||
Noise | 48-54 dBA at 1m | 53-60 dBA at 1m | ||
Protection rating | IP20 | |||
Efficiency | >91% up to 98% | >92% up to 98% | ||
Compliance | Safety EN 50091-1-1 EMC EN 50091-2 Directives 73/23-93/68-89/336 EEC | |||
Weight (kg) | from 190 to 460 | from 200 to 470 | from 220 to 490 | from 230 to 500 |
Dimensions (mm) (LxDxH) | 555x720x1200 | |||
Back-up (min) Internal | from 0 to 50 | from 0 to 40 | from 0 to 20 | from 0 to 15 |