AR POWER SOLUTION
A R P O W E R S O L U T I O N
Logo

Single Phase UPS

Introducing AR Power's latest innovation, the AR PowerMAX. This cutting-edge double-conversion online UPS boasts an impressive output power factor of 0.9, delivering unparalleled power density and a remarkable 12.5% increase in power compared to conventional UPS units with similar specifications.

Equipped with advanced DSP (Digital Signal Processing) technology and active input power factor correction, the AR PowerMAX ensures superior output voltage stability, power quality, and performance under all circumstances. With its dual mains inputs, this UPS guarantees unmatched power reliability, even in regions plagued by poor power conditions. Experience the next level of power protection and performance with AR PowerMAX.

Features

  • Experience the pinnacle of power protection with our online double conversion UPS technology.
  • Achieve unmatched efficiency with an input power factor corrector (PFC) rating of 0.99, ensuring optimal power utilization.
  • Benefit from automatic bypass functionality, seamlessly transferring the load to mains power in the event of overload or internal faults.
  • With an impressive output power factor of 0.9, our PowerPro series delivers robust power delivery capabilities.
  • Choose between single-phase input and output configurations or opt for three-phase input with single-phase output on our 20KVA model, providing flexibility to suit your specific needs.
  • Ensure uninterrupted power to critical applications with our hot standby configuration, guaranteeing the availability of quality power when it matters most.
  • Our battery cold start feature allows the UPS to be powered on directly from the battery, ensuring continuous operation even in the absence of utility power.
  • Scale your power capacity and enhance redundancy by paralleling up to three units effortlessly.
  • Enjoy the flexibility of configurable battery options, allowing you to tailor the UPS to your unique requirements with ease.

Technical Data Specifications

THREE PHASE/ SINGLE PHASE MODELS Harga Satuan (Rp.), Eskalasi (Varian 15%)
08 (3/1) 10 (3/1) 15 (3/1) 20 (3/1)
INPUT
Rated power (kVA) 8 10 15 20
Rated voltage (V) 400 Vac three-phase
Voltage range ±20%
Frequency range 45/65 Hz
Power factor 0.8 (0.9 in CLEAN version)
BYPASS
Rated current (A) 35 43 65 87
Rated voltage (V) 230 Vac single-phase
Permitted voltage range ±15% (selectable from ±10% to ±25% from front panel)
Rated frequency 50/60 Hz (autorange)
Permitted frequency range ±2% (selectable from ±1% to ±5% from front panel)
Standard features BackFeed protection; separate bypass line
BATTERIES
Type Maintenance-free sealed lead-acid
Maximum recharge current (A) 0.2xC10
RECTIFIER OUTPUT
Maintenance Voltage Variable acc. to temperature (-0.5 Vx°C)
Ripple <1%
INVERTER OUTPUT
Rated power (kVA) 8 10 15 20
Rated voltage (V) 6.4 8 12 16
Number of phases single-phase
Rated voltage (V) 220/230/240
Rated current (A) 35 43 65 87
Regulation of output voltage 200-244 V phase/neutral (from control panel) ±5%
Crest factor (Ipeak/Irms) 3:1
Waveform Sinewave
Static stability ±1%
Dynamic stability ±5% in 5ms
Frequency same as the input (autorange)
Overload 125% 150% 200% of the rated current for 10'/1'/7"
Frequency stability ±0.05% on mains failure
±2% (selectable from ±1% to ±5% from front control panel) with mains supply present
ENVIROMENTAL Remote Signalling volt free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm, output 0.5A/42V)
Remote Controls EPO and bypass
Operating temperature 0-40°C
Relative humidity 95% (non condensing)
Color Light grey RAL 7035
Noise 48-54 dBA at 1m 53-60 dBA at 1m
Protection rating IP20
Efficiency >91% up to 98% >92% up to 98%
Compliance Safety EN 50091-1-1 EMC EN 50091-2 Directives 73/23-93/68-89/336 EEC
Weight (kg) from 190 to 460 from 200 to 470 from 220 to 490 from 230 to 500
Dimensions (mm) (LxDxH) 555x720x1200
Back-up (min) Internal from 0 to 50 from 0 to 40 from 0 to 20 from 0 to 15